Removing hardness also reduces the need for expensive chemical treatment to control scale. Cleaver-Brooks water softeners are available in package design for virtually any commercial or industrial application. A water softener is recommended whenever raw hardness exceeds 1 ppm. Water softeners are available for boilers of all sizes, including multiple boiler applications, steam or hot water.
Models SMR and FMR
Available in single-, twin- or triplex tank designs and include resin tank(s), brine tank, face-piping, diaphragm valve nest and cycle controller. They feature carbon steel tanks with epoxy lined interiors and utilizes water activated diaphragm valves and an electronic controller.
Features:
Sized from 20,000 to 1,500,000 grains exchange capacity
Flow rates from 2 to 450 gpm
Galvanized steel exterior piping with cast iron fittings
NEMA 4 electrical enclosures
Optional skid mounted and pre-piped, pre-wired systems
Optional ASME code stamped tanks
Models FSE and SSE
Available in single-, twin- or triplex tank designs and include resin tank(s), brine tank, resin, piping, multi-position top-mounted piston valves, flow meters and electronic demand controller. FSE model has plastic tanks for easy installation. SSE model has steel tanks with top-mounted valves.
Features:
Sized from 20,000 to 1,200,000 grains exchange capacity
Flow rates from 8 to 350 gpm
Tank sizes 9″ to 48″ diameter standard, larger available
Operating temperatures: 40° to 100°F
Spray-lined steel or FRP plastic tanks
Optional skid-mounted and pre-piped, pre-wired systems
Optional ASME code-stamped tanks
Model CRS
Crossover twin alternating systems with plastic tanks and a single top-mounted valve that controls both tanks. Includes resin tanks, brine tank, single valve with CRS controller and interconnecting piping. They provide a continuous supply of softened water with one tank in service and one tank in either regenerating or in standby. Solid-state CRS controls provide a simple, reliable operation.
Features:
Sized from 15,000 to 450,000 grains exchange capacity
Flow rates from 12 to 45 gpm
Tank sizes 7″ to 30″ diameter
Operating temperatures: 40° to 100°F
Water meter for automatic regeneration
Optional skid mounted